Electric fire monitoring system should be set up for the non-fire power load of nursing facilities for the elderly. The following buildings or places should be equipped with electric fire monitoring system with non-fire power load:
1 Class B, Class C workshops and Class C warehouses with building height greater than 50m, and workshops (warehouses) with outdoor fire water consumption greater than 30L/s;
A class of high-rise civil buildings;
3/kloc-cinemas and theaters with more than 0/500 seats, gymnasiums with more than 3,000 seats, and the construction area of any floor exceeds 3,000 m? Public buildings such as shopping malls and exhibition buildings, radio and television, telecommunications, financial and trade buildings at or above the provincial (city) level, etc. whose outdoor fire water consumption is more than 25L/s;
4. Key brick-wood ancient buildings of national cultural relics protection units.
Standard for Electrical Design of Civil Buildings (GB5 1348-20 19) stipulates that:
In addition to the current national standard "Code for Fire Protection of Building Design" GB? In addition to the buildings or places specified in 500 16, the electrical fire monitoring system shall be installed in the non-fire load distribution circuit of the following civil buildings or places:
1 Civil airport terminal, Class I and II bus stations, Class I and II port passenger stations;
Hotel buildings, shopping malls and supermarkets with a total construction area of over 3000m2;
3/KLOC-More than 0/500 cinemas and theaters, more than 3,000 gymnasiums, more than 2,000 auditoriums and more than 20,000 stadiums;
Libraries with more than 500,000 books;
5 provincial and above museums, art galleries, cultural centers, science and technology museums and other public buildings;
Ward building and outpatient building of Grade III B and above hospitals;
7. Provincial and municipal power dispatching buildings, telecommunications buildings, postal buildings, disaster prevention command dispatching buildings, radio and television buildings and archives buildings;
8. Urban rail transit and first-class traffic tunnel projects;
9. Song, dance, entertainment and projection entertainment places on the first, second and third floors underground, semi-underground or on the ground, and the construction area of any floor is more than 300 square meters;
10 kindergartens, boarding houses for primary and secondary schools, and foster facilities for the elderly.